• Language


BAU (Bank-Level Management)

The BCU manages the battery rack and is typically installed in the high-voltage control box. It measures rack voltage, current and insulation resistance, calculates SOC and SOH, and provides fault diagnosis and protection. CAN, daisy-chain, RS485 and Ethernet interfaces enable communication with the BMU, BAU, PCS and EMS.
Product certifications

Product Specifications

ParameterDescription
ProcessorQuad-core 64-bit Cortex-A55 / 2.0 GHz
Memory2 GB LPDDR4
Operating SystemLinux
Display10.1" capacitive touchscreen, resolution 1280×800
Communication ProtocolsModbus RTU, Modbus TCP, IEC104, IEC61850
Battery Management CapabilityUp to 500 series × 60 clusters
Interfaces 
— CAN3 isolated channels, rate 250k/500 kbps
— RS4859 isolated channels, rate 9600–57600 bps
— DI18 channels (7 active-high, 11 active-low)
— Dry contact output16 channels, max 32 V, max 500 mA
— High-side output4 channels, max 24 V, max 500 mA
— Ethernet4 ports (2 Gigabit, 2 Fast Ethernet)
— TYPE-C1
— USB3 ports; read/write speed depends on the USB drive, typ. 5 MB/s
— TF1 TF slot; read/write speed depends on the TF card, typ. 3 MB/s
— Wi-Fi1
— HDMI1
— 4G1 (domestic and global roaming supported)
Environment 
— Supply voltageDC 12–32 V
— Power consumption<10 W
— Operating temperature−20 ℃ ~ 65 ℃
— Storage temperature−40 ℃ ~ 85 ℃
— Relative humidity5%–95%, non-condensing
— Altitude<4000 m
Enclosure 
— DimensionsExterior: 288 mm × 190 mm × 43 mm; Cutout: 266 mm × 179 mm
— MaterialABS+PC, black fine-textured matte finish
— Flammability ratingUL94-V0
Email